                         assembling instruction
            earth fault and short circuit indicator type ekl4
                        (panel instrument)
descrition
the earth fault and shot circuit indicator consists of:        
l           1 pc reading instrument (panel instrument)
l           3 pcs sensors for detecting short circuit current
l           4 pcs linght cable
l           1 pc sensor for observing the sum current
l           1 pc flashing lamp (optional)
installation of the reading instrument
the earth fault and short circuit indicator is designed for panel installation .the necessary dimensions of the cutout are 91.5+0,6x44.5+0,6mm ( refer to figure 2 ) .before sliding in the instrument , the electrical connections can be accomplished .the housing is slded into the opening and pushed with a light pressure up to stop position .springs ( figure l ) serve to keep the reading instrument in its position .
installation of the light cable
the sensor which is installed on the cable,is connected to
the reading instrument via light cable.therefore the sensor
of core l 1has to be connected with the terminal l1 on the
back of the reading instrument.(the endings of the light
cables have to be pushed into the pick-up openings up to
stop position.)the same has to be done with the sensors l2,
l3 and the earth fault sensor 14(figure 3).
power supply
the power supply is performed via a 3.6 v lithium
 

battery.for exchanging the battery,a screw cap
on the front side of the indication housing must
be removed by turning it left.the battery must be
taken out and replaced by a new one.(with the
supply via lithium battery,the 230 vac are only
connected in case the erath fault and short circuit
indicator type ek shall be reset also via recovering
voltage of the net.)
electric connection
depending one the version,the electrical connection has to be done according to the designations in figure 3.
terminals without any marking(nc)are without any function.in principle,the information indicated on the reading instrument is valid.
setting the display time
the time of displaying after a short circuit or earth is
adjustable.
there are three times to choose.the standard reste times are:1-2
 
-4h(other values are possible).the adjustment of the reset times
will be done by a rotaryswitch.the rotary switche is on the front
side of the indicator in the left top corner.the possible switch
positions are shown if figure 4.
setting the operating points for short circuit
the adjustment of the operating points of the earth fault and shore circuit indicator indicator type ekl4 is done at the sensors.three different operating points can be adjusted.the operating points are adjusted with a rotary switch at the front side of the sensor.the adjustable operating points are indicated on the front side of the sensor.
 
所属分类:中国电工电气网 / 高压成套电器
本页链接:/product/1753987.asp
故障指示器 面板型、电缆型、架空型的文档下载: PDF DOC TXT
关于广州旭旺电力科技有限公司商铺首页 | 更多产品 | 联系方式 | 黄页介绍
主要经营:面板型、电缆型、架空型故障指示器,
本公司坐落于中国广东省广州市,供应高品质故障指示器,,欢迎惠顾!故障指示器由传感器和显示器两部分组成,传感器负责探测电缆通过的电流,显示器负责对传感器传送来的电流信息进行判断及做出故障指示动作。在线 ...
顺企网 | 公司 | 黄页 | 产品 | 采购 | 资讯 | 免费注册 轻松建站
免责声明:本站信息由企业自行发布,本站完全免费,交易请核实资质,谨防诈骗,如有侵权请联系我们   法律声明  联系顺企网
© 11467.com 顺企网 版权所有
ICP备案: 粤B2-20160116 / 粤ICP备12079258号 / 粤公网安备 44030702000007号 / 互联网药品信息许可证:(粤)—经营性—2023—0112